| STEP | ACTION |
| 1 | Pull the handle down for all four PDU breakers which are S-03, S-04, S-02 and S-01. This will disconnect the power for the PDU's or Power Drive Units. |
| 2 | A lock will be placed through each handle for each breaker to prevent the handle from being turned back on. With the locks will be a tag explaining who is working on the drive motors and the reason why. |
| 3 | Then pull the switch down for the S-05 breaker that is beside the PDU2 cabinet. This will turn off power to the antenna as well. A lock will then be placed on the switch with a tag explaining who is working on the drive motors and the reason why. |
| 4 | Then pull the switch down for the single phase 120V power in behind the servo computer or OCU. This will turn off power to the singal phase power in the interface cabinet. This is a red switch located at the top right corner in behind the servo computer rack OCU. A lock will then be placed on the switch with a tag explaining who is working on the drive motors and the reason why. |